RS/M 28 - 50
Modulating • 198 - 2,201 MBTUH

RS/1 28 - 38
On-Off • 617 - 1,761 MBTUH




RS/M Model 28 38 50
Capacity (MBTUH)(1) 198 - 1,232 266 - 1,665 321 - 2,201
Combustion
Air Motor
Voltage(2)(3) 120/1/60 120/1/60 or 230-460-575/3/60 230-460-575/3/60
HP 1/2 1/2 or 3/4 3/4
Amperage Draw 5.2 5.2 / 3.2 / 1.6 / 1.3 3.2 / 1.6 / 1.3
Sound Levels dBA 68.0 70.0 72.0
Max. Chamber Pressure ("w.c.) @ high fire 1.2 1.4 1.0
Min. Gas Pressure ("w.c.)(4)(5) 6.0 7.0 6.0
(1) Ratings based on 1,000 Btu/ft.3 and .64 specific gravity.
(2) Other voltages available on request.
(3) A seperate 120/1/60 control voltage supply is required.
(4) Based on natural gas.
(5) Honeywell, Dungs and Siemens gas trains available.

 

RS/1 Model 28 38
Capacity (MBTUH)(1) 617 - 1,320 880 - 1,761
Combustion
Air Motor
Voltage(2)(3) 120/1/60 120/1/60
HP 1/2 1/2
Amperage Draw 5.2 5.2
Sound Levels dBA 70.0 72.0
Max. Chamber Pressure ("w.c.) @ high fire 0.6 0.7
Min. Gas Pressure ("w.c.)(4)(5) 6.0 7.0
(1) Raitings based on 1,000 Btu/ft.3 and .64 specific gravity.
(2) Other voltages available on request.
(3) A seperate 120/1/60 control voltage supply is required.
(4) Based on natural gas.
(5) Honeywell, Dungs and Siemens gas trains available.